1295 FIXED SERIES - TEST REPORT
CLICK HERE FOR 1295 FIX SERIES - SPECIFICATIONS
CLICK HERE FOR 1295 FIX SERIES - DRAWING

AAMA/NWWDA 101/I.S.2-97 TEST REPORT

Rendered to:

REPCO
510 Station Avenue
Bensalem, Pennsylvania 19020

Report No: ATI-18495
Test Date: 11/29/96
Report Date: 12/12/96
Expiration Date: 11/29/00


Series/Model: 1295

Type: Thermally Improved Aluminum Fixed Window

Project Summary

Architectural Testing Inc. (ATI) was contracted by Repco to perform structural tests on a Series 1295 Fixed Window. The sample tested successfully met the performance requirements for a Class F-HC55. The test specimen description and test data are reported below.

Test Specification

The test specimen was evaluated in accordance with AAMA/NWWDA 101-93, Voluntary Specification for Aluminum and Poly (Vinyl Chloride) (PVC) Prime Windows and Glass Doors.

Test Specimen Description  
Overall Size 6'0'' wide by 6'0'' high
Daylight Opening Size 5'9-1/8'' wide by 5'9-1/8'' high
Finish All aluminum was painted brown
Glazing The window utilized 0.85'' thick sealed insulating glass fabricated from two 0.185'' thick, clear sheets of annealed glass and a desiccant-filled metal spacer system. The insulating glass was interior drop-in glazed using mastic compound. On the interior side was a silicone heal bead and an aluminum snap-in glazing bead with a ¼'' diameter flexible bulb seal.
Frame Contruction Frame members were constructed of extruded aluminum that employed a poured-in place urethane thermal break with an average debridged width of 0.173''. All corners were coped, butted, sealed and fastened with two screws per corner.

Test Results
The results are tabulated as follows:

Paragraph Title of Test - Test Method Results Allowed
2.1.2 Air Infiltration    
  @ 1.56 psf (25 mph) 0.03 cfm/ft --
  @ 6.24 psf (50 mph) 0.03 cfm/ft 0.15 cfm/ft
2.1.3 Water resistance    
  WTP = 6.00 psf No entry No entry
  @ 5.00 gph/ft2    
2.1.4 Uniform Load Structural    
  @ 60.0 psf (exterior) 0.001" 0.288"
  @ 60.0 pasf (interior) 0.001" 0.288"
Optional Performance
3.3 Water Resistance    
  WTP = 12.0 psf No entry No entry
  @ 5.00 gph/ft2    
3.4 Uniform Load Structural    
  @ 82.5 psf (exterior) 0.040" 0.288"
  @ 82.5 psf (interior) 0.010" 0.288"

Representative samples of the test specimen and a copy of this report will be retained by ATI for a period of four years. This report is the exclusive property of the client so named herein and is applicable to the sample tested. Results obtained are tested values and do not constitute an opinion or endorsement by this laboratory.

For ARCHITECTURAL TESTING INC.

Matthew J. Sindlinger Bruce W. Croak
Technician Project Manager

MJS:cat
18495

 

 